Modern businesses comply with safety regulations because they genuinely believe in minimising harm to their people and the environment.  They know that incidents cause distress to those affected and are generally more expensive than the cost of compliance.

For businesses with cost as a primary motivation, the following story illustrates how insurance companies use a relatively minor non-compliance to reject an expensive claim.

The story is real, but client identifying details have been removed.

Background
In 2011, a mining camp in remote Western Australia was operating a diesel tank, to provide fuel dispensing for site vehicles.

The diesel tank was required to comply with the WA DG Regulations, and Australian Standard 1940 (Storage and Handling of Flammable and Combustible Liquid).

An incident occurred when a mining contractor failed to turn off the fuel dispenser pump after refuelling his vehicle, spilling several thousand litres of diesel to ground.

Investigation
A pressure relief valve and bypass line was fitted downstream of the fuel transfer pump, to prevent the pump from “dead heading” when the fuel dispenser was not being used; fuel could flow back to the tank via the bypass line.

The pressure relief valve was set low enough that in addition to protecting the pump, it also leaked a small flow of diesel back into the tank during refuelling.

Adjacent to the pressure relief valve, was an isolation valve.  Operators had discovered that closing the isolation valve would result in maximum flow to the dispenser, and therefore faster refuelling.

The incident occurred when a mining contractor closed the isolation valve for faster refuelling, but when finished, forgot to turn off the pump and return the isolation valve to “open”.

The fuel pump continued to “dead head” until it overheated and failed, causing a loss of fuel to the environment.

Insurance Claim
An insurance claim was made for the loss of diesel and environmental remediation.  Lawyers for the insurer investigated the incident, and argued that:

  • Because the mine operator could not provide a compliance assessment for the diesel tank, pipe, and pump system, it was deemed to be “non-compliant” with the DG Regulations and AS1940.
  • Based on the pipe and pump system being “non-compliant”, failure to turn off the fuel pump after use was therefore “not the cause” of the fuel spill.

Conclusion
Since the mine operator did not have a compliance assessment for the diesel tank, pipe, and pump system, they could not demonstrate compliance with AS1940.  Consequently, the insurance claim was rejected.

If a dangerous goods assessment had been completed when the diesel tank was commissioned, it would have:

  • Provided the compliance assessment required by the insurer, and,
  • Identified that the isolation valve must be removed from the pressure bypass line, and therefore, the incident would not have occurred in the first place.